1, Capacitive voltage transformer common exception handling table
Serial number |
Exception description |
Treatment |
Treatment measures |
1 |
Tank partial oil leakage, oil level visible |
Site processing |
Check to confirm leakage, plugging, fill the oil |
2 |
The electromagnetic unit oil level exceeds the upper limit |
Site processing |
For the products put into operation if the secondary voltage fluctuations at the same time, contact the manufacturer service department;
|
3 |
Transformer abnormal noise, odor or vibration, there is abnormal voltage display |
Site processing |
Check the secondary wiring, to ensure that no secondary wiring short circuit, N, XL reliable grounding |
4 |
|
Site processing |
Remove the secondary wiring board at the pollution and wipe clean with alcohol, can not be restored, please contact the manufacturer Service |
5 |
|
Site processing |
Check the test methods, lines and equipment, if the test is no exception to contact the manufacturer service department |
6 |
Other exceptions |
/ |
Please contact the manufacturer's service department |
2, oil-immersed current transformer common exception handling table
Serial number |
Exception description |
Treatment |
Treatment measures |
1 |
Current transformer oil leakage, oil level visible |
Site processing |
Check to confirm leakage, plugging, fill the oil |
2 |
Put the oil level above the upper limit |
Site processing |
Put the oil to the right level |
3 |
The transformer has an abnormal sound |
Site processing |
Check the secondary wiring, to ensure that the secondary wiring is no open, no virtual access |
4 |
DC resistance abnormal |
|
Check the test wiring, clean the clamping part of the oxide layer, retest |
5 |
Current ratio test is abnormal |
Site processing |
Check a series-parallel connection, check the test wiring, improve the test current |
6 |
Expander (cover) from the top |
Replace the product |
Exit immediately |
7 |
Other exceptions |
/ |
Please contact the manufacturer's service department |
3, SF6 voltage transformer common exception handling table
Serial number |
Exception description |
Treatment |
Treatment measures |
1 |
Treatment measures |
Site processing |
1, the controller to remove the check, if the replacement of the controller;
|
2 |
SF6 PT operates with secondary discharge sound |
Site processing |
Check whether the circuit short-circuit phenomenon, the secondary voltage is abnormal, unused winding is open. |
3 |
SF6 PT low resistance to ground insulation |
Site processing |
Check the insulation casing surface is dirty or damp, clean again after treatment. |
4 |
|
Site processing |
If the measurement error at the control cabinet will increase the system error caused by the lead voltage drop from the SF6 PT secondary wiring board to the HSBC cabinet, the SF6 PT error test will not be carried out. qualified. It is required to carry out error test at SF6 PT secondary wiring board to reduce systematic error. |
5 |
SF6 PT after the operation of the third harmonic, and the three-phase third-harmonic amplitude is basically the same, the phase is identical, open-triangle output voltage is essentially zero. |
Site processing |
Check the secondary circuit, the existence of virtual line virtual connection. |
6 |
A group of JDQX-35 products (3) a secondary output voltage is low, and the opening triangle abnormal voltage |
Site processing |
Substation power failure to carry out the following pilot projects:
|
7 |
|
Site processing |
Substation power failure to check the three-phase PT residual winding connection meets the requirements (three remaining winding requirements of the first and last connection). |
8 |
Rupture disk |
Replace the product |
Exit immediately |
9 |
Other exceptions |
/ |
Please contact the manufacturer's service department |
4, SF6 current transformer common exception handling table
Serial number |
Exception description |
Treatment |
Treatment measures |
1 |
Site controller alarm |
Site processing |
1, the controller to remove the check, if the replacement of the controller;
|
2 |
Current ratio test is abnormal |
Site processing |
Check a series-parallel connection, check the test wiring, improve the test current |
3 |
Rupture disk Replace the product |
|
Replace the product |
4 |
Other exceptions |
/ |
Please contact the manufacturer's service department |
5, pouring current transformer common exception handling table
Serial number |
common problem |
Treatment |
solution |
1 |
Products than the test correct, after the installation of secondary current anomalies |
Site processing |
1, check the transformer secondary terminal of the lead wire is burr lap; |
2 |
Generator outlet (into the line cabinet) bus-type transformer and a copper discharge transformer |
Site processing |
Check whether the transformer shield wire is firmly fixed with the primary copper wire |
6, cast voltage transformer common exception handling table
Serial number |
common problem |
Treatment |
solution |
1 |
Open delta voltage is not correct |
Site processing |
Check the three-phase voltage transformer residual winding wiring is connected end to end |
2 |
Fuse frequent fuse |
Site processing |
1, check the secondary circuit for short circuit; |